Installation
D-011-0152 27
.
Figure 12 EA800 Console Wired 4-20mA Sensor Connections
Programming
When powered-up, the EA800 is ready for programming. The following is an overview of the general process for
programming the EA800:
View the MAIN MENU and unlock the EA800 as described in “Accessing the MAIN MENU for Programming” on
page 28.
Set the system configuration as described in “Configuring System Parameter Settings” on page 28.
Add the wireless sensors. See the appropriate subsection under “Adding Wireless Sensors” on page 29.
Add the wired sensors. See the appropriate subsection under “Adding Wired Sensors” on page 32.
Verify performance of the wireless sensors. See “Verify Wireless Signal Strength” on page 31.
Configure the relays. See “Configuring the Relays” on page 34.
Note: When no sensors are programmed in the EA800 system, the EA800 console boots up with a 30-minute
delay before the alarm buzzer sounds. At this time the Alarm screen is displayed with a System Alarm
caused by the fact that no sensors have been programmed yet. To prevent the System Alarm from acti-
vating, you must program at least one connected sensor into the EA800 console prior to the end of the
30-minute alarm time-out. If the alarm buzzer sounds press the Alarm Silence key to temporarily silence
the alarm buzzer.
4-20mA Sensors
(3-wire)
EA800
Console
Powered
External
Adapter
Powered
J6
Input N
User
supplied
cable
4-20mA
Transmitter
Connector
NC
J5
Aux Power Out
J6
Input N
User
supplied
cable
NC
J5
Aux Power Out
External
Power
Adapter
4-20mA
Transmitter
Connector
4-20mA
Output
4-20mA
Output
4-20mA Sensors
(2-wire)
J6
Input N
User
supplied
cable
4-20mA
Transmitter
Connector
NC
J5
Aux Power Out
EA800 Console
J6
Input N
User
supplied
cable
NC
J5
Aux Power Out
External
Power
Adapter
4-20mA
Transmitter
Connector
4-20mA
Output
4-20mA
Output
4-20mA Sensors
(4-wire)
J6
Input N
User
supplied
cable
4-20mA
Transmitter
Connector
NC
J5
Aux Power Out
J6
Input N
User
supplied
cable
NC
J5
Aux Power Out
External
Power
Adapter
4-20mA
Transmitter
Connector